Cable Construction
Conductor: The conductors shall be solid, annealed and bare copper with a diameter of AWG23 and
minimum acceptable diameter shall be 0.546mm.
Insulation: Each conductor shall be insulated with HDPE or FEP (In case of Plenum grade). The insulation shall be uniform and shall not have any defects. The diameter over the insulation shall be maximum 1.22mm.
Non-continuous shield: The non-continuous aluminum tape shall be applied over the core wrapping to
increase alien crosstalk performances. 
Sheath: The flame retardant PVC or LSZH(Low Smoke Zero Halogen) compound colored grey or other
colors shall be applied over the cable core.
Electrical Performance

Characteristics

Units

Specification

DC Resistance

Ω/100m

≤ 9.38

DC Resistance Unbalance

%

≤ 5.00

Capacitance Unbalance
(Pair to Ground)

pF/km
(800~1000Hz)

≤ 330

Insulation Resistance

MΩ-100m

≥ 500

Dielectric Strength

DC kV/sec

2.5 / 2

Impedance

(Characteristic mean)

Ω

100 ± 15% (1 ≤ f ≤ 500MHz)

Return Loss dB/100m ≥ 20 + 5 * log(freq)         , 1      ≤ f <  10MHz
≥ 25                                   , 10  ≤ f < 20MHz
≥ 25 – 7 * log(freq/20) , 20  ≤ f ≤ 500MHz
Attenuation
(Insertion Loss)
dB/100m ≤ 1.82*√(freq) + 0.0091*(freq) + 0.25/√(freq)
, 1 ~ 500 MHz
NEXT Loss dB/100m ≥ 44.3 – 15*log(freq/100) , 1 ~ 500MHz
Power sum NEXT Loss dB/100m ≥ 42.3 – 15*log(freq/100) , 1 ~ 500MHz
ELFEXT Loss dB/100m ≥ 27.8 – 20*log(freq/100) , 1 ~ 500MHz
Power sum ELFEXT Loss dB/100m ≥ 24.8 – 20*log(freq/100) , 1 ~ 500MHz
Propagation Delay dB/100m ≤ 534 + 36 / √ (Freq) , 1 ~ 500MHz
Propagation Delay Skew dB/100m ≤ 45 , 1 ~ 500MHz
CPR Compliant
- The LSZH product comply with CPR reaction to fire : Dca-s2-d2-a1